NTT Com-Netmagic Datacenter - BSE Mumbai
Facility Specification  

NTT Com-Netmagic Datacenter - P.J. Towers, Mumbai (BSE Building)

Facility Specification

 

LOCATION

Area Fort, Mumbai, India
Access 30 minutes by road from Mumbai International Airport
 
 

BUILDING SPECIFICATION

Dedicated/Shared server room space
Raised Floor Load Bearing Capacity 1,250 kgs/sq. mt.

DATACENTER DESIGN STANDARD

TIER III +

POWER

Power Receiving 1 commercial power company
UPS UPS system with N+N redundancy
Generator Gen-set with N redundancy
Power Provision Dual power feed, PDU sources to each rack Power supply to a rack: 3.0 – 6.0 kVA

COOLING

System Air-cooling system with N+1 redundancy Management of temperature and humidity
Blow-out Type Raised flooring air conditioning system Down-blow below raised floor and drawn into ceiling

FIRE PROTECTION

VESDA Smoke Detectors
FM 200 Inert gas based Fire Security System

SECURITY

Camera Monitoring cameras
Guard 24x7 on-site security presence
Building Access Photo ID required
Room Access Access card and biometric authentication

CONNECTIVITY

Truly Carrier Neutral with domestic peering capabilities
Carriers Available Bharti Airtel | MTNL | TCL | TTSL | Tulip | Reliance

STANDARD RACK

Type Front and rear perforated door
Size (WxDxH) 600mm × 1000mm × 2100mm (42U)